Overview
This is a guide on how to test a redundant iFIX and Historian iFIX collector environment. As well as preforming development updates to a redundant iFIX server pair.
Pre-Requisites
- iFIX 5.X redundant SCADA servers configured.
- Historian collectors configured for redundancy.
Testing iFIX and Historian Redundancy
- Open SCADASYNCMONITOR.exe
on both secondary and Primary iFIX servers
- Check which SCADA server
is ACTIVE
- Open Historian
Administrator
- Check which iFIX
collector is in ACTIVE status
- For this document I will
assume that the Primary node is ACTIVE in both SCADASYNCMONITOR and Historian
Administrator (iFIX collector)
- With SCADASYNC monitor
open Enable Maintenance Mode to make the Secondary SCADA node ACTIVE
- Ensure all data is coming
into iFIX
- Within Historian
Administrator Select Collectors > select Secondary iFIX collector >
select Redundancy Tab > Make Active Collector Now
- Navigate back to Main and
ensure the Secondary collector is now Active and Primary collector is
Standby
- Navigate to Tags and
ensure Tags are still collecting good data
- We have now confirmed that
the Secondary iFIX node should be able to run the SCADA environment and
collect good Historical DATA without the Primary Node.
- Ensure Maintenance Mode
is no longer enabled.
When using Maintenance Mode, the following events must
occur:
- Make the secondary node
the active node using the NSD fields. Wait for the iClient nodes to switch
to the secondary node.
- You place the primary node
into Maintenance Mode by clicking the Enable Maintenance Mode button.
- You enter your database
changes on the primary node.
- You take the primary node
out of Maintenance Mode by clicking the Disable Maintenance Mode button.
- The primary node becomes
the active node. The secondary node becomes standby.
- You save your database.
The databases are re-synchronized.
- To do this ensure the
secondary node is still active within SCADASYNCMONITOR and Historian
Administrator
- Ensure Maintenance Mode
is no longer enabled.
- I.E. Primary Node is in
Standby for both iFIX and Proficy Historian
- Once that is complete SHUT
DOWN the secondary node.
- Within ~30 seconds the
Primary SCADA node should become ACTIVE within SCADASYNCMONITOR and
Historian administrator
- Check iFIX Workspace and
ensure that data is populating and there are no @@@ signs.
- Check Historian
Administrator > Tags to see data is collecting with a good value